LIMIT STATE DESIGN: BASIS FOR DESIGN
The current revision of the code
of practice, IS 800:2000, recommends limit state method for design of
structures using hot rolled sections. This method is outlined in section 5 of
IS 800:2007. However, it retained working stress method of design which was the
design method for decades. But the scope of the working stress method is
limited to those situations where limit state method cannot be conveniently
employed.
BASIS FOR DESIGN
In the limit state design method,
the structure shall be designed to withstand safely all loads likely to act on
it throughout its life. It shall not suffer total collapse under accidental
loads such as from explosions or impact or due to consequences of human error
to an extent beyond the local damages. The objective of the design is to
achieve a structure that will remain fit for use during its life with
acceptable target reliability. In other words, the probability of a limit state
being reached during its lifetime should be very low. The acceptable limit for
the safety and serviceability requirements before failure occurs is called a
limit state. In general, the structure shall be designed on the basis of the
most critical limit state and shall be checked for other limit states.
Steel structures are to be
designed and constructed to satisfy the design requirements with regard to
stability, strength, serviceability, brittle fracture, fatigue, fire, and
durability such that they meet the following: a) Remain fit with adequate
reliability and be able to sustain all actions (loads) and other influences
experienced during construction and use; b) Have adequate durability under
normal maintenance; c) Do not suffer overall damage or collapse
disproportionately under accidental events like explosions, vehicle impact or
due to consequences of human error to an extent beyond local damage. The
potential for catastrophic damage shall be limited or avoided by appropriate
choice of one or more of the following:
•
Avoiding, eliminating or
reducing exposure to
hazards, which the
structure is likely
to
sustain.
• Choosing structural
forms, layouts and details and designing such that: i) the structure has low sensitivity
to hazardous conditions; and ii) the structure survives with only local damage
even
after serious damage to any one individual element by the
hazard.
• Choosing suitable
material, design and detailing procedure, construction specifications, and control
procedures for shop fabrication and field construction as relevant to the
particular structure.
The
following conditions may be satisfied to avoid a disproportionate collapse: The
building should be effectively tied together at each principal floor level and
each column should be effectively held in position by means of continuous ties
(beams) nearly orthogonal, except where the steel work supports only cladding
weighing not more than 0.7 kN/m2 along with imposed and wind loads.
These ties must be steel members such as beams, which may be designed for other
purposes, steel bar reinforcement anchoring the steel frame to concrete floor
or steel mesh reinforcement in composite slab with steel profiled sheeting
directly connected to beam with shear connectors. These steel ties and their
end connections should be capable of resisting factored tensile force not less
than the factored dead and imposed loads acting on the floor area tributary to
the tie nor less than 75 kN. Such connection of ties to edge column should also
be capable of resisting 1 percent of the maximum axial compression in the
column at the level due to factored dead and imposed loads. All column splices
should be capable of resisting a tensile force equal to the largest of a
factored dead and live load reaction from a single floor level located between
that column splice and the next column splice below that splice. Lateral load
system to resist notional horizontal loads prescribed in Cl. 4.3.6 of IS
800:2007 should be distributed throughout the building in nearly orthogonal
directions so that no substantial portion is connected at only one point to
such a system. Precast concrete or other heavy floor or roof units should be
effectively anchored in the direction of their span either to each other over
the support or directly to the support. Where the above conditions to tie the
columns to the floor adequately are not satisfied each storey of the building
should be checked to ensure that disproportionate collapse would not
precipitate by the notional removal, one at a time, of each column. Where each
floor is not laterally supported by more than one system, check should be made
at each storey by removing one such lateral support system at a time to ensure
that disproportionate collapse would not occur. The collapse is considered
disproportionate, if more than 15 percent of the floor or roof area of 70 m2
collapse at that level and at one adjoining level either above or below it,
under a load equal to 1.05 or 0.9 times the dead load, 0.33 times temporary or
full imposed load of permanent nature (as in storage buildings) and 0.33 times
wind load acting together.
Related Topics
Privacy Policy, Terms and Conditions, DMCA Policy and Compliant
Copyright © 2018-2023 BrainKart.com; All Rights Reserved. Developed by Therithal info, Chennai.