Home | | Power Quality | IEEE and IEC Standards

Chapter: Power Quality : Harmonics

IEEE and IEC Standards

1. Overview of IEC 2. IEC 61000 – 2 – 2 3. IEC 61000 – 3 - 2

IEEE and IEC Standards:

 

It should be emphasized that the philosophy behind this standard seeks to limit the harmonic injection from individual customers so that they do not create unacceptable voltage distortion under normal system characteristics and to limit the overall harmonic distortion in the voltage supplied by the utility. The voltage and current distortion limits should be used as system design values for the worst case of normal operating conditions lasting more than 1 h. For shorter periods, such as during start-ups, the limits may be exceeded by 50 percent.

 

This standard divides the responsibility for limiting harmonics between both end users and the utility. End users will be responsible for limiting the harmonic current injections, while the utility will be primarily responsible for limiting voltage distortion in the supply system.

 

The harmonic current and voltage limits are applied at the PCC. This is the point where other customers share the same bus or where new customers may be connected in the future. The standard seeks a fair approach to allocating a harmonic limit quota for each customer. The standard allocates current injection limits based on the size of the load with respect to the size of the power system, which is defined by its short-circuit capacity. The short-circuit ratio is defined as the ratio of the maximum short-circuit current at the PCC to the maxi mum demand load current (fundamental frequency component) at the PCC as well.

 

The basis for limiting harmonic injections from individual customers is to avoid unacceptable levels of voltage distortions. Thus the current limits are developed so that the total harmonic injections from an individual customer do not exceed the maximum voltage distortion shown in Table 4.8. Table 4.8 shows harmonic current limits for various system voltages. Smaller loads (typically larger short-circuit ratio values) are allowed a higher percentage of harmonic currents than larger loads with smaller short-circuit ratio values. Larger loads have to meet more stringent limits since they occupy a larger portion of system load capacity. The current limits take into account the diversity of harmonic currents in which some harmonics tend to cancel out while others are additive. The harmonic current limits at the PCC are developed to limit individual voltage distortion and voltage THD to the values shown in Table 4.1. Since voltage distortion is dependent on the system impedance, the key to controlling voltage distortion is to control the impedance.

 

 

The two main conditions that result in high impedance are when the system is too weak to supply the load adequately or the system is in resonance. The latter is more common. Therefore, keeping the voltage distortion low usually means keeping the system out of resonance. Occasionally, new transformers and lines will have to be added to increase the system strength. IEEE Standard 519-1992 represents a consensus of guidelines and recommended practices by the utilities and their customers in minimizing and controlling the impact of harmonics generated by nonlinear loads.

 

Table 4.8 Basis for Harmonic Current Limits

 


 

1. Overview of IEC standards on harmonics

 

The International Electro technical Commission (IEC), currently with headquarters in Geneva, Switzerland, has defined a category of electromagnetic compatibility (EMC) standards that deal with power quality issues. The term electromagnetic compatibility includes concerns for both radiated and conducted interference with end-use equipment. The IEC standards are broken down into six parts:

 

   Part 1: General. These standards deal with general considerations such as introduction, fundamental principles, rationale, definitions, and terminologies. They can also describe the application and interpretation of fundamental definitions and terms. Their designation number is IEC 61000-1-x.

 

    Part 2: Environment. These standards define characteristics of the environment where equipment will be applied, the classification of such environment, and its compatibility levels. Their designation number is IEC 61000-2-x.

 

 

    Part 3: Limits. These standards define the permissible levels of emissions that can be generated by equipment connected to the environment. They set numerical emission limits and also immunity limits. Their designation number is IEC 61000-3-x.

 

  Part 4: Testing and measurement techniques. These standards provide detailed guidelines for measurement equipment and test procedures to ensure compliance with the other parts of the standards. Their designation number is IEC 61000-4-x.

 

    Part 5: Installation and mitigation guidelines. These standards provide guidelines in application of equipment such as ear thing and cabling of electrical and electronic systems for ensuring electromagnetic compatibility among electrical and electronic apparatus or systems. They also describe protection concepts for civil facilities against the high-altitude electromagnetic pulse (HEMP) due to high altitude nuclear explosions. They are designated with IEC 61000-5- x.

 

 Part 6: Miscellaneous. These standards are generic standards defining immunity and emission levels required for equipment in general categories or for specific types of equipment.

 

Their designation number is IEC 61000-6-x. IEC standards relating to harmonics generally fall in parts 2 and 3. Unlike the IEEE standards on harmonics where there is only a single publication covering all issues related to harmonics, IEC standards on harmonics are separated into several publications. There are standards dealing with environments and limits which are further broken down based on the voltage and current levels. These key standards are as follows:

 

  IEC 61000-2-2 (1993): Electromagnetic Compatibility (EMC). Part 2: Environment. Section

 

2:    Compatibility Levels for Low-Frequency Conducted Disturbances and Signaling in Public Low-Voltage Power Supply Systems.

 

   IEC 61000-3-2 (2000): Electromagnetic Compatibility (EMC). Part 3: Limits. Section 2: Limits for Harmonic Current Emissions (Equipment Input Current Up to and Including 16 A per Phase).

 

   IEC 61000-3-4 (1998): Electromagnetic Compatibility (EMC). Part 3: Limits. Section 4: Limitation of Emission of Harmonic Currents in Low-Voltage Power Supply Systems for Equipment with Rated Current Greater Than 16 A.

 

■ IEC 61000-3-6 (1996): Electromagnetic Compatibility (EMC). Part 3: Limits. Section 6: Assessment of Emission Limits for Distorting Loads in MV and HV Power Systems. Basic EMC publication. Prior to 1997, these standards were designated by a 1000 series numbering scheme. For example, IEC 61000-2-2 was known as IEC 1000-2- 2. These standards on harmonics are generally adopted by the European Community (CENELEC); thus, they are also designated with the EN 61000 series. For example, IEC 61000-3-2 is also known as EN 61000-3-2.

 

2. IEC 61000-2-2

 

IEC 61000-2-2 defines compatibility levels for low-frequency conducted disturbances and signaling in public low-voltage power supply systems such as 50- or 60-Hz single- and three-phase systems with nominal voltage up 240 and 415 V, respectively. Compatibility levels are defined empirically such that they reduce the number of complaints of mis operation to an acceptable level.15 these levels are not rigid and can be exceeded in a few exceptional conditions. Compatibility levels for individual harmonic voltages in the low-voltage network are shown in Table 6.7. They are given in percentage of the fundamental voltage.

 

3. IEC 61000-3-2 and IEC 61000-3-4

 

Both IEC 61000-3-2 and 61000-3-4 define limits for harmonic current emission from equipment drawing input current of up to and including 16 Aper phase and larger than 16 Aper phase, respectively. These standards are aimed at limiting harmonic emissions from equipment connected to the low-voltage public network so that compliance with the limits ensures that the voltage in the public network satisfies the compatibility limits defined in IEC 61000-2-2. The IEC 61000-3-2 is an outgrowth from IEC 555-2 (EN 60555-2). The standard classifies equipment into four categories:

 

 Class A: Balanced three-phase equipment and all other equipment not belonging to classes B, C, and D

 

 Class B: Portable tools.

 

 Class C: Lighting equipment including dimming devices

 

 

■ Class D: Equipment having an input current with a “special wave shape” and an active input power of less than 600 W

 

Figure 4.32 can be used for classifying equipment in IEC 61000-3-2. It should be noted that equipment in classes B and C and provisionally motor-driven equipment are not considered class D equipment regardless of their input current wave shapes. The half-cycle wave shape of class D equipment input current should be within the envelope of the inverted T-shape shown in Fig. 4.33 for at least 95 percent of the time. The center line at /2 lines up with the peak value of the input current Ipk. Maximum permissible harmonic currents for classes A, B, C, and D are given in actual amperage measured at the input current of the equipment. Note that harmonic current limits for class B equipment are 150 percent of those in class A. Harmonic current limits according to IEC 61000-3-2 are shown in Tables 6.8 through 6.10. Note that harmonic current limits for class D equipment are specified in absolute numbers and in values relative to active power. The limits only apply to equipment operating at input power up to 600 W. IEC 61000-3-4 limits emissions from equipment drawing input current larger than 16 A and up to 75 A. Connections of this type of equipment do not require consent from the utility. Harmonic current limits based on this standard are shown in Table 4.3.

 

Table 4.3 Harmonic Current Limits According to IEC 61000-3-4






Study Material, Lecturing Notes, Assignment, Reference, Wiki description explanation, brief detail
Power Quality : Harmonics : IEEE and IEC Standards |


Privacy Policy, Terms and Conditions, DMCA Policy and Compliant

Copyright © 2018-2024 BrainKart.com; All Rights Reserved. Developed by Therithal info, Chennai.