Chapter: Electrical machines : Synchronous Generator

Armature Reaction - Synchronous Generator

To illustrate this important point, we shall consider the following three cases: 1. When load p.f. is unity 2. When load p.f. is zero lagging 3. When load p.f. is zero leading

Armature Reaction

 

When an alternator is running at no-load, there will be no current flowing through the armature winding. The flux produced in the air-gap will be only due to the rotor ampere turns. When the alternator is loaded, the three-phase currents will produce a totaling magnetic field in the air-gap. Consequently, the air-gap flux is changed from the no-load condition.

 

The effect of armature flux on the flux produced by field ampere turns (i. e., rotor ampere turns) is called armature reaction.

 

Two things are worth noting about the armature reaction in an alternator. First, the armature flux and the flux produced by rotor ampere-turns rotate at the same speed (synchronous speed) in the same direction and, therefore, the two fluxes are fixed in space relative to each other.

 

Secondly, the modification of flux in the air-gap due to armature flux depends on the magnitude of stator current and on the power factor of the load. It is the load power factor which determines whether the armature flux distorts, opposes or helps the flux produced by rotor ampere-turns.

 

 

To illustrate this important point, we shall consider the following three cases:

 

1.             When load p.f. is unity

 

2.             When load p.f. is zero lagging

 

3.             When load p.f. is zero leading

 

When load p.f. is unity


Above Fig: 1 (c) shows an elementary alternator on no load. Since the armature is on open-circuit, there is no stator current and the flux due to rotor current is distributed symmetrically in the air-gap as shown in Fig: 1 (d). Since the direction of the rotor is assumed clockwise, the generated e.m.f. in phase R1R2 is at its maximum and is towards the paper in the conductor R1 and outwards in conductor R2. No armature flux is produced since no current flows in the armature winding.

 

Fig (ii) shows the effect when a resistive load (unity p.f.) is connected across the terminals of the alternator. According to right-hand rule, the current is "in" in the conductors under N-pole and "out" in the conductors under S-pole. Therefore, the armature flux is clockwise due to currents in the top conductors and anti-clockwise due to currents in the bottom conductors. Note that armature flux is at 90° to the main flux (due to rotor current) and is behind the main flux.

 

In this case, the flux in the air-gap is distorted but not weakened. Therefore, at unity p.f., the effect of armature reaction is merely to distort the main field; there is no weakening of the main field and the average flux practically remains the same. Since the magnetic flux due to stator currents (i.e., armature flux) rotate; synchronously with the rotor, the flux distortion remains the same for all positions of the rotor.

 

When load Power Factor is Zero lagging

 

When a pure inductive load (zero p.f. lagging) is connected across the terminals of the alternator, current Fig: 1 (c) shows the condition when the alternator is supplying resistive load. Note that e.m.f. as well as current in phase R1R2 is maximum in the position shown. When the alternator is supplying a pure inductive load, the current in phase R1R2 will not reach its maximum value until N-pole advanced 90° electrical as shown in Fig: 1 (d). Now the armature flux is from right to left and field flux is from left to right All the flux produced by armature current (i.e., armature flux) opposes be field flux and, therefore, weakens it. In other words, armature reaction is directly demagnetizing. Hence at zero p.f. lagging, the armature reaction weakens the main flux. This causes a reduction in the generated e.m.f.

 

When load Power Factor is Zero leading

 

 

When a pure capacitive load (zero p.f. leading) is connected across the terminals of the alternator, the current in armature windings will lead the induced e.m.f. by 90°.


Obviously, the effect of armature reaction will be the reverse that for pure inductive load. Thus armature flux now aids the main flux and the generated e.m.f. is increased. Fig: 1 (c) shows the condition when alternator is supplying resistive load.

Note that e.m.f. as well as current in phase R1R2 is maximum in the position shown. When the alternator is supplying a pure capacitive load, the maximum current in R1R2 will occur 90° electrical before the occurrence of maximum induced e.m.f. Therefore, maximum current in phase R1R2 will occur if the

 

position of the rotor remains 90° behind as compared to its position under resistive load. This is illustrated in Fig: 1 (d). It is clear that armature flux is now in the same direction as the field flux and, therefore, strengthens it. This causes an increase in the generated voltage. Hence at zero p.f. leading, the armature reaction strengthens the main flux.

 

For intermediate values of p.f, the effect of armature reaction is partly distorting and partly weakening for inductive loads. For capacitive loads, the effect of armature reaction is partly distorting and partly strengthening. Note that in practice, loads are generally inductive.